9.0 Standard EIA/TIA 568
The ANSI/EIA/TIA-568-1991 Standard _Commercial Building
Telecommunications Wiring Standard_ defines pinouts;
9.1 Standard EIA/TIA T568A
(also called ISDN, previously called EIA)
Pin Wire Color
=== ==========
/--T3 1 White/Green
Pair3 \--R3 2 Green
/----------T2 3 White/Orange
/ /-R1 4 Blue
pair2 \ pair1 \-T1 5 White/Blue
\----------R2 6 Orange
/--T4 7 White/Brown
pair4 \--R4 8 Brown
9.2 Standard EIA/TIA T568B
(also called AT&T specification, previously called 258A)
/--T2 1 White/Orange
pair2 \--R2 2 Orange
/----------T3 3 White/Green
/ /-R1 4 Blue
pair3 \ pair1 \-T1 5 White/Blue
\----------R3 6 Green
/--T4 7 White/Brown
pair4 \--R4 8 Brown
9.3 USOC (Universal Service Order Code)
8-pins 6-pins
| |
/-------------T4 1 White/Brown
/ /---------T3 2 1 White/Green
/ / /-----T2 3 2 White/Orange
/ / / /-R1 4 3 Blue
pr4\ pr3\ pr2\ pr1\-T1 5 4 White/Blue
\ \ \-----R2 6 5 Orange
\ \---------R3 7 6 Green
\-------------R4 8 Brown